Star Delta Motor Terminal Diagram
A practical reference for 6-terminal three-phase motor star and delta wiring, including U1 V1 W1 / U2 V2 W2 terminal links, contactor sequence, overload placement and common nameplate checks.
โš ๏ธ Important: Star-delta starting is suitable only when the motor can run in delta at the supply voltage. On a 400 V supply, the motor nameplate is usually expected to show 400 ฮ” / 690 Y. Check the motor nameplate before wiring.
๐Ÿ”Œ Visual terminal box reference: Star vs Delta links
6-terminal motor connection: Star start and Delta run Typical IEC terminal marking: top row U1 V1 W1, bottom row W2 U2 V2 STAR (Y) CONNECTION Used during starting to reduce phase voltage and starting current Motor terminal box U1 V1 W1 W2 U2 V2 Link W2 + U2 + V2 together L1L2L3 Starting modeLower current and lower starting torque DELTA (ฮ”) CONNECTION Used during normal run when motor is rated for delta at line voltage Motor terminal box U1 V1 W1 W2 U2 V2 Link U1-W2 ยท V1-U2 ยท W1-V2 L1L2L3 Running modeFull voltage and normal running torque
Search wiring note
Filter group
Quick filters:
ItemConnection / MeaningGroupPractical note
Star supplyL1 โ†’ U1, L2 โ†’ V1, L3 โ†’ W1STARSupply goes to the start ends of the three windings.
Star pointLink W2 + U2 + V2 togetherSTARThe three lower terminals are shorted as one common star point.
Delta linksU1-W2, V1-U2, W1-V2DELTAThese three vertical links form the delta winding loop.
Delta supplyL1, L2, L3 feed the three linked pairsDELTAIn normal run, each winding sees full line-rated phase voltage.
Starter sequenceMain + Star ON โ†’ open transition โ†’ Main + Delta ONCONTROLStar and delta contactors must be electrically and mechanically interlocked.
TimerStar time usually a few seconds, then transfer to deltaCONTROLSet just long enough for the motor to accelerate near rated speed.
Overload relayLine-side or inside-delta depending on panel designCONTROLInside-delta overload setting is typically 0.58 ร— motor FLA.
Nameplate check400 ฮ” / 690 Y is typical for 400 V star-delta useSAFETYDo not run a 230 ฮ” / 400 Y motor in delta on a 400 V supply.
RotationSwap any two incoming phases to reverse directionSAFETYVerify rotation before coupling pumps, fans, conveyors or compressors.
Step 1
Main + Star
starting period
Step 2
Open gap
transition delay
Step 3
Main + Delta
normal running
โœ… In a standard open-transition star-delta starter, the delta contactor should never close while the star contactor is still closed. Use both mechanical and electrical interlocking.
โš ๏ธ Too-short star time causes high current during transition. Too-long star time can make the motor run weakly, overheat, or fail to accelerate under load.
Good for 400 V star-delta
Nameplate400 ฮ” / 690 Y
Supply400 V
RunDelta
Not for 400 V delta run
Nameplate230 ฮ” / 400 Y
Supply400 V
RunStar / VFD check
Terminal requirement
Motor leads6 terminals
LabelsU1 V1 W1 / U2 V2 W2
Starter3 contactors
โŒ If the motor has only three accessible terminals, a conventional star-delta starter cannot change the winding connection externally.

๐Ÿ“‹ Quick Reference

โญ Star links
SupplyU1 V1 W1
Common linkW2-U2-V2
๐Ÿ”บ Delta links
Link 1U1-W2
Link 2V1-U2
Link 3W1-V2
โš™๏ธ Current / torque
Star line currentโ‰ˆ 1/3 DOL
Star torqueโ‰ˆ 1/3 DOL
Delta runfull voltage

๐Ÿ“š Field Notes

Terminal layout matters Many IEC motors use top row U1 V1 W1 and bottom row W2 U2 V2, but always confirm the terminal box diagram.
Star-delta reduces torque Starting torque is also reduced, so it is not ideal for heavily loaded starts such as loaded conveyors or compressors.
Overload setting depends on location A line-side overload is normally set to motor FLA. Inside-delta overload often uses 0.58 ร— FLA.
Check alternatives For frequent starts, heavy loads or smooth acceleration, compare with a soft starter or VFD.

Star Delta Motor Terminal Diagram

This star delta wiring reference explains how to connect a six-terminal three-phase induction motor in star for starting and delta for normal running. It shows the common U1, V1, W1, W2, U2 and V2 terminal layout used in many motor terminal boxes.

How star delta starting works

In star mode, the motor windings receive reduced phase voltage, so starting current and starting torque are lower than direct-on-line starting. After the motor accelerates, the starter opens the star contactor and closes the delta contactor for normal full-voltage running.

โ“ Frequently Asked Questions

Connect L1 to U1, L2 to V1, L3 to W1, then link U2, V2 and W2 together as the star point.
For the common IEC terminal layout, link U1-W2, V1-U2 and W1-V2. Connect the three supply lines to those three linked pairs.
Usually a motor marked 400 ฮ” / 690 Y is suitable for star-delta starting on a 400 V supply because it runs in delta at 400 V.
Normally no. A 230 ฮ” / 400 Y motor is designed to run in star on 400 V, not in delta on 400 V.
Common causes include wrong terminal links, wrong phase sequence, too-short acceleration time, heavy load, contactor overlap, low voltage, mechanical jamming or wrong overload setting.
There is no universal value. It is usually set long enough for the motor to reach near rated speed before transfer, often a few seconds depending on load inertia.
It may be installed in line or inside delta depending on the panel design. The setting changes with the location, so follow the wiring diagram and relay manual.
Yes, line starting current is typically reduced to about one-third of DOL, but starting torque is also reduced to about one-third.